Event-Triggered Non-Linear Control of Offshore MMC Grids for Asymmetrical AC Faults

Naajein Cherat*, Vaibhav Nougain, Milovan Majstorović, Peter Palensky, Aleksandra Lekić

*Corresponding author for this work

Research output: Chapter in Book/Conference proceedings/Edited volumeConference contributionScientificpeer-review

Abstract

Fault ride-through capability studies of MMC-HVDC connected wind power plants have focused primarily on the DC link and onshore AC grid faults. Offshore AC faults, mainly asymmetrical faults have not gained much attention in the literature despite being included in the future development at national levels in the ENTSO-E HVDC code. The proposed work gives an event-triggered control to stabilize the system once the offshore AC fault has occurred, identified, and isolated. Different types of control actions such as proportional-integral (PI) controller and super-twisted sliding mode control (STSMC) are used to smoothly transition the post-fault system to a new steady state operating point by suppressing the negative sequence control. Initially, the effect of a negative sequence current control scheme on the transient behavior of the power system with a PI controller is discussed in this paper. Further, a non-linear control strategy (STSMC) is proposed which gives quicker convergence of the system post-fault in comparison to PI control action. These post-fault control operations are only triggered in the presence of a fault in the system, i.e., they are event-triggered. The validity of the proposed strategy is demonstrated by simulation on a ±525 kV, three-terminal meshed MMC-HVDC system model in Real Time Digital Simulator (RTDS).

Original languageEnglish
Title of host publicationIEEE PES Innovative Smart Grid Technologies Europe, ISGT EUROPE 2024
EditorsNinoslav Holjevac, Tomislav Baskarad, Matija Zidar, Igor Kuzle
PublisherIEEE
Number of pages5
ISBN (Electronic)9789531842976
DOIs
Publication statusPublished - 2024
Event2024 IEEE PES Innovative Smart Grid Technologies Europe Conference, ISGT EUROPE 2024 - Dubrovnik, Croatia
Duration: 14 Oct 202417 Oct 2024

Publication series

NameIEEE PES Innovative Smart Grid Technologies Europe, ISGT EUROPE 2024

Conference

Conference2024 IEEE PES Innovative Smart Grid Technologies Europe Conference, ISGT EUROPE 2024
Country/TerritoryCroatia
CityDubrovnik
Period14/10/2417/10/24

Bibliographical note

Green Open Access added to TU Delft Institutional Repository ‘You share, we take care!’ – Taverne project https://www.openaccess.nl/en/you-share-we-take-care
Otherwise as indicated in the copyright section: the publisher is the copyright holder of this work and the author uses the Dutch legislation to make this work public.

Keywords

  • asymmetrical AC faults
  • fault ride-through
  • MMC-HVDC based power system
  • negative sequence control
  • offshore wind farms

Fingerprint

Dive into the research topics of 'Event-Triggered Non-Linear Control of Offshore MMC Grids for Asymmetrical AC Faults'. Together they form a unique fingerprint.

Cite this