TY - JOUR
T1 - Exergoeconomic and environmental analyses of CO2/NH3 cascade refrigeration systems equipped with different types of flash tank intercoolers
AU - Mosaffa, A. H.
AU - Farshi, L. Garousi
AU - Infante Ferreira, C. A.
AU - Rosen, M. A.
N1 - Accepted Author Manuscript
PY - 2016
Y1 - 2016
N2 - Exergoeconomic and environmental analyses are presented for two CO2/NH3 cascade refrigeration systems equipped with (1) two flash tanks and (2) a flash tank along with a flash intercooler with indirect subcooler. A comparative study is performed for the proposed systems, and optimal values of operating parameters of the system are determined that maximize the coefficient of performance (COP) and exergy efficiency and minimize the total annual cost. The operating parameters considered include condensing temperatures of NH3 in the condenser and CO2 in the cascade heat exchanger, the evaporating temperature of CO2 in the evaporator, the temperature difference in the cascade heat exchanger, the intermediate pressure of the flash tank in the CO2 low-temperature circuit, the mass flow rate ratio in the flash intercooler and the degree of superheating of the CO2 at the evaporator outlet. The total annual cost includes the capital, operating and maintenance costs and the penalty cost of GHG emission. The results show that, the total annual cost rate for system 1 is 11.2% and 11.9% lower than that for system 2 referring to thermodynamic and economic optimizations, respectively. For thermodynamic and cost optimal design condition the COP and exergy efficiency of both systems are almost the same. Finally, in order to obtain the best balance between exergy destruction cost and capital cost, the exergoeconomic factor is defined for each component of proposed systems, for cases in which the system operates at the best performance conditions.
AB - Exergoeconomic and environmental analyses are presented for two CO2/NH3 cascade refrigeration systems equipped with (1) two flash tanks and (2) a flash tank along with a flash intercooler with indirect subcooler. A comparative study is performed for the proposed systems, and optimal values of operating parameters of the system are determined that maximize the coefficient of performance (COP) and exergy efficiency and minimize the total annual cost. The operating parameters considered include condensing temperatures of NH3 in the condenser and CO2 in the cascade heat exchanger, the evaporating temperature of CO2 in the evaporator, the temperature difference in the cascade heat exchanger, the intermediate pressure of the flash tank in the CO2 low-temperature circuit, the mass flow rate ratio in the flash intercooler and the degree of superheating of the CO2 at the evaporator outlet. The total annual cost includes the capital, operating and maintenance costs and the penalty cost of GHG emission. The results show that, the total annual cost rate for system 1 is 11.2% and 11.9% lower than that for system 2 referring to thermodynamic and economic optimizations, respectively. For thermodynamic and cost optimal design condition the COP and exergy efficiency of both systems are almost the same. Finally, in order to obtain the best balance between exergy destruction cost and capital cost, the exergoeconomic factor is defined for each component of proposed systems, for cases in which the system operates at the best performance conditions.
KW - Cascade refrigeration system
KW - CO/NH
KW - Environmental analysis
KW - Exergoeconomic analysis
KW - Flash tank
KW - Optimization
UR - http://www.scopus.com/inward/record.url?scp=84962221250&partnerID=8YFLogxK
UR - http://resolver.tudelft.nl/uuid:818ecf28-631b-4c8c-a78f-3750b38ccd99
U2 - 10.1016/j.enconman.2016.03.053
DO - 10.1016/j.enconman.2016.03.053
M3 - Article
AN - SCOPUS:84962221250
VL - 117
SP - 442
EP - 453
JO - Energy Conversion and Management
JF - Energy Conversion and Management
SN - 0196-8904