Partial discharge pattern analysis of modelled insulation defects in transformer insulation

F Massingue, S Meijer, P Agoris, JJ Smit, J Lopez-Roldan

    Research output: Chapter in Book/Conference proceedings/Edited volumeConference contributionScientific

    Abstract

    This paper describes the first results from experimental investigations which have been carried out to study the partial discharge phenomena in power transformer insulation. Using different types of modeled insulation defects and ageing tests it is aimed to organize a database of known defects, which will be used for recognition of discharges of unknown sources of defects. Moreover, the first results of the investigation of degradation processes of pressboard during ageing are described. The experiments were carried out using the classical IEC 60270 method and the UHF method. Phase resolved patterns of the defects were collected for statistical analysis. Different defects were discriminated using cluster analysis.
    Original languageUndefined/Unknown
    Title of host publicationConference record of the 2006 IEEE international symposium on electrical insulation
    Editors s.n.
    Place of PublicationPiscataway
    PublisherIEEE Society
    Pages542-545
    Number of pages4
    ISBN (Print)1-4244-0334-0
    Publication statusPublished - 2006
    Event2006 IEEE international symposium on electrical insulation, Toronto - Piscataway
    Duration: 11 Jun 200617 Jun 2006

    Publication series

    Name
    PublisherIEEE

    Conference

    Conference2006 IEEE international symposium on electrical insulation, Toronto
    Period11/06/0617/06/06