A soft start-up method for DC micro-grid based on improved two-level VSC with DC fault ride-through capability

Weijie Wen, Rui Lyu*, Botong Li, Hong Cao, Jiali Yu, Bin Li, Marjan Popov

*Corresponding author for this work

Research output: Contribution to journalArticleScientificpeer-review

28 Downloads (Pure)

Abstract

For the black start-up of DC micro-grids, three-phase charging resistors are required to limit the uncontrollable surge current. The main drawback of this start-up method is the difficulty in determining the appropriate resistance value to achieve a rapid start-up and limit the surge current with the change of grid parameters. To address this problem, this article proposes a soft start-up method for the DC micro-grid based on an improved two-level voltage source converter (VSC). Specifically, an silicon controlled rectifier and anti-parallel diode are added in each up-bridge-arm in the improved VSC. By conducting a dynamic control strategy of the firing angle on the SCRs, the start-up current can always be maintained near a given value to achieve rapid start-up. Moreover, the improved VSC has DC fault ride-through capability. The simulation results based on PSCAD/EMTDC are provided to validate the feasibility of the proposed start-up method.

Original languageEnglish
Article number1079099
Number of pages10
JournalFrontiers in Energy Research
Volume11
DOIs
Publication statusPublished - 2023

Keywords

  • AC-DC converter
  • control method
  • DC micro-gird
  • start-up
  • topology

Fingerprint

Dive into the research topics of 'A soft start-up method for DC micro-grid based on improved two-level VSC with DC fault ride-through capability'. Together they form a unique fingerprint.

Cite this