Abstract
Existing line protection methods for multi-terminal direct current (MTDC) systems are constrained by the placement and values of boundary elements. To overcome this limitation, this paper proposes a non-unit DC line protection method based on the normalized backward traveling waves (BTWs) of the 1-mode voltage. Firstly, this article studies the traveling wave characteristics and derives the expressions for the normalized BTWs. Then, the Levenberg-Marquardt algorithm is used for amplitude fitting and normalization calculation. Based on the normalized BTWs, a non-unit protection method is proposed. Finally, the proposed method is evaluated with a simulation model on the PSCAD/EMTDC platform. The results demonstrate that the proposed method can accurately identify faults of different resistances and distances without requiring boundary devices, and is robust against noise disturbances (35 dB).
Original language | English |
---|---|
Title of host publication | Proceedings of 2023 IEEE PES Innovative Smart Grid Technologies Europe, ISGT EUROPE 2023 |
Publisher | IEEE |
Number of pages | 5 |
ISBN (Electronic) | 9798350396782 |
DOIs | |
Publication status | Published - 2023 |
Event | 2023 IEEE PES Innovative Smart Grid Technologies Europe, ISGT EUROPE 2023 - Grenoble, France Duration: 23 Oct 2023 → 26 Oct 2023 |
Publication series
Name | IEEE PES Innovative Smart Grid Technologies Conference Europe |
---|
Conference
Conference | 2023 IEEE PES Innovative Smart Grid Technologies Europe, ISGT EUROPE 2023 |
---|---|
Country/Territory | France |
City | Grenoble |
Period | 23/10/23 → 26/10/23 |
Bibliographical note
Green Open Access added to TU Delft Institutional Repository ‘You share, we take care!’ – Taverne project https://www.openaccess.nl/en/you-share-we-take-careOtherwise as indicated in the copyright section: the publisher is the copyright holder of this work and the author uses the Dutch legislation to make this work public.
Keywords
- Levenberg-Marquardt algorithm
- Modular multilevel converter
- Multi-terminal DC grid
- Non-unit protection
- Traveling wave